MV XGN2-12 Fixed Metal-enclosed Switchgear for Frequent Operation Occasions
A MV XGN2-12 fixed metal-enclosed switchgear.
MV XGN2-12 fixed metal-enclosed switchgear.
MV XGN2-12 fixed metal-enclosed switchgear is used to receive and distribute power energy in electrical power system of three-phase, AC, 50 Hz and 3.6 kV, 7.2 kV and 12 kV voltage. It is
especially suitable for frequent operation occasions. It meets the standards of GB3906 and IEC298. The main switch adopts ZN63-12 and ZN65A-12 integrated vacuum circuit breaker. Disconnecting
switch adopts GN30-12 rotating disconnecting switch, GN22-12 high current disconnecting switch and GN30-12 rotating high current disconnecting switch.
The model and meaning of MV XGN2-12 fixed metal-enclosed switchgear.
Working conditions:
Altitude: ≤ 1000 m.
Temperature range: -25 °C to +40 °C.
Relative air humidity: daily: ≤ 95%, monthly: ≤ 90%.
Seismic intensity: ≤ 8 degree.
Workplaces should be free of fire, explosion, serious pollution, chemical corrosion and severe vibration.
Note: if switchgear is installed in the areas where altitude is higher than 1000 m, please contact with manufacturer to take measure of enlarge insulation.
Technical parameters of MV XGN2-12 fixed metal-enclosed switchgear
No. Items Parameters
1 Rated voltage (kV) 3.6, 7.2, 12
2 Rated current (A) 630 - 3150
3 Maximum working current (A) 630, 1000, 1250, 2000, 2500, 3150
4 Rated short-circuit breaking current (kA) 20, 31.5, 40
5 Rated short time withstand current (kA) 20, 31.5, 40
6 Rated peak withstand current (kA) 50, 80, 100
7 Rated making current (kA) 50, 80, 100
8 Thermal stabilization time (s) 4
9 Protection degree IP2X
10 Weight (kg) 400 - 700
11 Overall size (width × depth × height) (mm) 1100 × 1200 × 2650 (1250 A and below)
1200 × 1200 × 2650 (1250 A above)
Technical parameters of ZN65-12 and ZN63-12 circuit breaker
Items Parameters
Rated voltage (kV) 12
Rated frequency (Hz) 50
Rated current (A) 1250, 2000, 2500, 3150
Rated short-circuit breaking current (kA) 20, 31.5, 40
Rated making current (kA) 50, 80, 100
Rated short-time withstand current (kA) 20, 31.5, 40
Rated peak withstand current (kA) 50, 80, 100
Thermal stable time (s) 4
Mechanical life (Times) 10000
Vacuum interrupter vacuum degree (Pa) ≥ 6.6 × 102
Arcing time (ms) ≤ 20
Rated short-circuit breaking current breaking times (Times) 30 (50)
Technical parameters of disconnecting switch
Items GN30-12/400-12.5 GN30-12/630-20 GN30-12/1250-31.5
GN30-12D/400-12.5 GN30-12D/630-20 GN30-12D/1250-31.5
Rated voltage (kV) 12
Rated current (A) 400 630 1250
Rated short-time withstand current (kA) 12.5 20 31.5
Rated peak withstand current (kA) 31.5 50 80
Rated insulation level Lightning impulse withstand voltage (kV) 75
1 min power frequency withstand voltage (kV) 42