1. General
The vacuum contactor is mainly used in the power system with AC 50Hz and rated voltage 7.2kV, for making or breaking circuit and to make electromagnetic starter with suitable protective device and F-C switchgear.
2. Working condition:
1) Altitude should not be over 1,000m;
2) Ambient temperature: -5~40°C;
3) Average temperature in 24 hour not exceed 35°C;
4) When the highest temperature is 40°C, the relative humidity should not be higher than 50%;
5) Pollution degree: class 3
Main models and technical parameters
Rated voltage: 7.2 kv
Control voltage: 380/220/110
Rated current: 160A, 250A, 400A, 630A, 800A, 1000A
Clearance: 3.5±0.3 mm
Over travel: 2±0.2 mm
Pressure: >85N
Main circuit power frequency withstand voltage: 32000 v
Auxiliary circuit power frequency withstand voltage: 2500 v
Control circuit power frequency withstand voltage: 2000 v
Making capacity: 10Ie,100 times
Breaking capacity: 8Ie,25 times
Limit opening current(A): 10Ie
Overload: 8Ie,10 s
Mechanism life: 1 million times
Weight: 25.5 KG
Note: “Ie” represents the rated current of main circuit
HVJ30-1.14/1000、1250 series AC vacuum contactor is applicable for AC 50HZ power system of rated voltage 1.14KV and rated current up to 1000 A~1250Ato open and close circuit, start and control AC motor frequently. It is suitable for composed magnetic starter with various ...
HVJ20 series vacuum contactor has higher rated current, smaller size and anti-dusty advantages. It can be used in AC50 ~ 60Hz, 2KV power system, rated current to 800A, for long distance making-breaking and frequent starting and controlling of AC motor. Rated voltage: 2 kv / 2 ...
1. Introduction JCZ5 7.2 kv vacuum contactor HVJ6-7.2series indoor high-voltage AC vacuum contactor has two types: One isMechanical holding type, the other is Electromagnetic holding type. It is applicable for three-phase AC 50HZ power system of rated voltage7.2KV and below and ...