range of product |
Modicon Quantum automation platform
|
|
---|---|---|
product or component type |
Latch/interrupt module
|
number of inputs |
16
|
|
---|---|---|
discrete input type |
Fast isolated
|
|
absolute maximum input |
30 V DC
|
|
voltage state 0 guaranteed |
-3...5 V
|
|
voltage state 1 guaranteed |
15...30 V
|
|
current state 0 guaranteed |
2...8 mA
|
|
current state 1 guaranteed |
<= 0.5 mA
|
|
response time |
130 µs Off-On
30 µs On-Off |
|
reverse polarity protection |
Internal in 30 V
|
|
isolation between channels |
500 V for 60 s AC
|
|
isolation between channels and bus |
1780 V for 60 s AC
|
|
bus current requirement |
400 mA
|
|
power dissipation |
2.0 W + (0.3 x number of points on)
|
|
mounting support |
Backplane for local architecture
|
|
marking |
CE
|
|
module format |
Standard
|
resistance to electrostatic discharge |
4 kV contact conforming to IEC 801-2
8 kV on air conforming to IEC 801-2 |
|
---|---|---|
resistance to electromagnetic fields |
10 V/m 80...2000 MHz conforming to IEC 801-3
|
|
ambient air temperature for operation |
0...60 °C
|
|
ambient air temperature for storage |
-40...85 °C
|
|
relative humidity |
95 % without condensation
|
|
operating altitude |
<= 5000 m
|
|
standards |
UL 508
|
|
product certifications |
CSA Class 1 Division 2
C-Tick DNV FM Class 1 Division 2 GOST UL |
Sustainable offer status |
Green Premium product
|
|
---|---|---|
RoHS (date code: YYWW) |
Compliant - since 0901 - Schneider Electric declaration of conformity Schneider Electric declaration of conformity
|
|
REACh |
Reference not containing SVHC above the threshold
|
|
Product environmental profile |
Available </..LI:characteristics-list__item>#id::#::#p_Doc_Oid" style="outline: 0px; color: rgb(66, 180, 230); cursor: pointer; display: inline-block;">End of life manual
|
|
Product end of life instructions |
Available
|