range of product |
Modicon Quantum automation platform
|
|
---|---|---|
product or component type |
Safety dc discrete output module
|
discrete output number |
16
|
|
---|---|---|
group of channels |
1
|
|
discrete output logic |
Positive logic (source)
|
|
addressing requirement |
4 output words
7 input words |
|
discrete output voltage |
19.2...30 V DC
|
|
absolute maximum output |
34 V
|
|
voltage drop |
<= 0.3 V 0.5 A
|
|
sensor power supply |
19.2...30 V
|
|
maximum load current |
<= 0.65 A each point
<= 10.04 A each group |
|
surge current |
2 A for 10 ms
|
|
response time |
<= 20 ms at state 0 to state 1
<= 20 ms at state 1 to state 0 |
|
leakage current |
0.5 mA 30 V
|
|
protection type |
With
|
|
load inductance |
Inductance(H) = 0.5/((current(A))² x (switching frequency(Hz)))
0.5 8 Hz |
|
fault indication |
Channel fault
Overload Power supply fault System fault |
|
associated fuse rating |
10 A
|
|
isolation between channels and bus |
1500 Vrms for 1 minute
|
|
isolation between group and bus |
1500 Vrms for 1 minute
|
|
power dissipation |
1.9 W + 0.65 I²
|
|
marking |
CE
|
|
local signalling |
1 LED green bus communication is present (Active)
1 LED red external fault detected (F) 16 LEDs green output status 16 LEDs red system failure, diagnostic of internal channel fault |
|
bus current requirement |
350 mA
|
product certifications |
CSA
CSA HazLoc C-Tick TÜV Rheinland (SIL2) UL |
---|
Sustainable offer status |
Green Premium product
|
|
---|---|---|
RoHS (date code: YYWW) |
Compliant - since 0749 - Schneider Electric declaration of conformity Schneider Electric declaration of conformity
|
|
REACh |
Reference not containing SVHC above the threshold
|
|
Product environmental profile |
Available </..LI:characteristics-list__item>#id::#::#p_Doc_Oid" style="outline: 0px; color: rgb(66, 180, 230); cursor: pointer; display: inline-block;">End of life manual
|
|
Product end of life instructions |
Available
|