Electrical parameters | |
---|---|
Accuracy class | 0.05%, 0.1%, 0.2% |
Resolution | 6”TFT (640×480) |
Power supply |
220V±10%, 50/60Hz Li-polymer battery (size (mm): 110x51x16, nominal output voltage: 7.2V, capacity: 5000mAh) Power line supply (U1, UN), 85V-265V 50/60Hz |
Communication port | RS232, USB |
Test voltage | |
Range | 0-480V |
Error |
±0.05% (30V-480V) ±0.1% (0V-30V) |
Harmonic | 2nd-63st |
Test current | |
Range (direct connection) | 1mA-20A |
Error (direct connection) |
±0.05% (100mA-20A) ±0.1% (10mA-100mA) |
Range (clamp CT) | 10mA-3000A |
Clamp CTs optional | 5A, 100A, 200A, 500A, 1000A, 2000A, 3000A |
Error (camp CT) |
±0.2% (100mA-100A) ±0.5% (100A-3000A) |
Harmonic | 2nd-63st |
Power measure error | |
Active power (direct connection) |
±0.05% (0.1A-20A) ±0.1% (0.01A-0.1A) |
Reactive power (direct connection) | ±0.1% (0.1A-20A) |
Energy measure error | |
Active energy (direct connection) |
±0.05% (0.1A-20A) ±0.1% (0.01A-0.1A) |
Reactive energy (direct connection) | ±0.1% (0.1A-20A) |
Phase angle | |
Range | 0°-360° |
Resolution | 0.01° |
Error | ±0.05° |
Frequency | |
Range | 45-65Hz |
Resolution | 0.001Hz |
Error | 0.002Hz |
Pulse input | |
Input channel | 2 |
Input level | 5-24V |
Input frequency | Max. 2MHz |
Pulse output | |
Energy constant | 180000imp/kWh, 1800imp/kWh, 180imp/kWh |
Pulse ratio | 1:1 |
Output level | 5V |
Function | |
Vector diagram | Yes |
Waveform | Yes |
Energy accumulation | Yes |
Test meter Type | 1P2W, 1P3W, 3P3W, 3P4W |
CT ratio test | Yes |
CT PT programmable | Yes |
Check wiring | Yes |
smart optical sampler | 1PC |
Data storage | 500sets |
Communication with PC | Yes |
Mechanical parameters | |
Instrument dimensions (W×H×D) (mm) | 220×138×61 |
Instrument Weight (kg) | 1.7 |
Carry case dimensions (W×H×D) (mm) | 450×320×185 |
Carry case (kg) | 8.5 |
Environmental conditions | |
Ambient temperature | -10°C to 55°C |
Relative humidity | 15%-85% |
The Height of above sea level | ≤3000m |
The instrument GF312D1 is a precision 0.05% AC energy meter testing instrument, mainly used to test three phase energy meter error on site, measure all various of AC parameters and CT ratio & phase error, it is also as three phase reference energy meter in the laboratory. ...