Electrical parameters | |
---|---|
Accuracy | 0.05%, 0.1% |
Power Supply | One Phase AC 100-265V, frequency 50/60Hz. |
AC Voltage Output | |
Range(U1,U2,U3) | 0-500V; 0-380V; 0-300V; |
Adjustment range | (0-120)%RG(1) |
Adjustment fineness | 0.01%RG, 0.1%RG, 1%RG, 10%RG as optional. |
Stability | 0.01%/120s |
Distortion | 0.3% (Non-capacitive load) |
Output load | each phase 25VA |
Accuracy | 0.05%RG or 0.02%RG |
AC Current Output | |
Range(I1,I2,I3) | 0-6A; 0-12A; 0-20A; 0-50A; 0-120A; |
Adjustment range | (0-100)%RG |
Adjustment fineness | 0.01%RG, 0.1%RG, 1%RG, 10%RG as optional. |
Stability | <0.01%/120s |
Distortion | ≤0.3% (Non-capacitive load) |
Max Output load | 20VA or 50VA; |
Accuracy | 0.05%RG |
Power Measurement | |
Active power output stability | <0.01%RG/120s |
Reactive power output stability | <0.02%RG/120s |
Active power measuring accuracy | 0.05%RG |
Reactive power measuring accuracy | 0.1%RG |
Phase Output | |
Output adjustment range | 0°-359.999° |
Output adjustment fineness | 10, 1, 0.1, 0.01 as optional. |
Resolution | 0.01° |
Accuracy | 0.02° |
Power Factor | |
Adjustment range | -1 ~ 0 ~ 1 |
Resolution | 0.0001 |
Measurement accuracy | 0.0005 |
Frequency Measurement | |
Range | 40Hz-70Hz |
Resolution | 0.001Hz |
Accuracy | 0.002Hz |
Voltage /Current/Harmonic Setting | |
Harmonic number | 2-63times |
Harmonic content | 0-40% |
Harmonic phase | 0-359.99 |
Harmonic setting accuracy | (10%±0.1%)RD(2) |
Power Energy Measurement Error | |
Active power energy | 0.05%RG |
Reactive power energy | 0.1%RG |
Power Pulse Output | |
Power pulse type | active pulse, reactive pulse |
Active power pulse output | 5V, 10mA |
Power Pulse Input | |
Energy pulse type | support active and reactive pulse, the highest frequency power pulse input is 200K. |
Communication Port | |
Communication Port | RS232, USB2.0 |
Standard | |
Standard |
IEC 62053-21,22, 23; IEC 60736; ANSI C12.20-2002; JJG 597-2005; JJG596-2012; JJG 1085-2013; JJF 68-2019; DL/T 826-2002; DL/T 1478-2015; DL/T 448-2016 |
Safety | |
Isolation protection | IEC 61010-1:2001 |
Measurement Category | 300 V CAT III, 600 V CAT II |
Degree of protection | IP42 |
Declaration of conformity | CE & CNAS certified |
Mechanical parameters | |
Dimensions (W×D×H) (mm) | 495x390x195 |
Weight (kg) | 12.8 |
Environmental conditions | |
Ambient temperature | -10°C to +50°C |
Relative humidity | 35%-85% |
(1) RG means range, the same as below; (2) RD means the setted harmonic content, harmonic can be a single output, also multiple output. |
NO. | Accuracy | Voltage range | Current Range | Weight |
---|---|---|---|---|
302D112001 | 0.10% | 0-500V | 0-120A | 22KG |
302D1120005 | 0.05% | 0-500V | 0-120A | 22KG |
302D15001 | 0.10% | 0-500V | 0-50A | 18KG |
302D150005 | 0.05% | 0-500V | 0-50A | 18KG |
302D12001 | 0.10% | 0-500V | 0-20A | 15.8KG |
302D120005 | 0.05% | 0-500V | 0-20A | 15.8KG |
302D11201 | 0.10% | 0-380V | 0-12A | 12.8KG |
302D112005 | 0.05% | 0-380V | 0-12A | 12.8KG |
302D1601 | 0.10% | 0-300V | 0-6A | 8KG |
302D16005 | 0.05% | 0-300V | 0-6A | 8KG |
The instrument GF312D1 is a precision 0.05% AC energy meter testing instrument, mainly used to test three phase energy meter error on site, measure all various of AC parameters and CT ratio & phase error, it is also as three phase reference energy meter in the laboratory. ...