Photovoltaic SPD for DC power, 1000VDC; In(8/20us): 20kA/phase, Imax: 40kA/phase; hot-pluggable; fault indication;
Features & Advantages of Photovoltaic SPD 1000VDC
Status indication:
Green: OK
Red: Failed
DC power surge protector modules can be replaced online.
Remote alarm output is optional, named with "F".
It is normally installed at the boundary of LPZ1 and LPZ2 or subsequent LPZs.
Parameter of Photovoltaic 1000V DC SPD
T2-1000
T2-1000F
Max. continuous operating voltage Ucpv 1000VDC
Short-circuit current rating Iscpv 1000A
Nominal discharge current In(8/20µs) 20kA
Max. discharge current Imax(8/20µs) 40kA
Voltage protection level Up 4kV
Recommended backup fuse 80A gG
Recommended grounding cable 6~35mm2
Response time 25ns
Residual current IPE <10μA
Remote alarm output 250VAC/0.5A;24VDC/0.5A
Housing protection grade(IEC60529) IP 20
Housing material/inflammability rating(UL94) PA66/V0
Testing standard IEC 61643-31
CHENZHU strives to provide high-quality products and services to meet the expectations of our customers and interested parties by delivering outstanding performance. We have special talents to
research and develop safety and automation system. Indeed, automation and safety are our interface products' main characters.