H3G-TH lead acid battery monitoring system is equipped with battery thermal runaway warning, high-accuracy SOC/SOH monitoring, and comprehensive intelligent analysis of the battery. This battery
monitoring system for lead acid battery can effectively ensure the safe operation of backup batteries in high-end data center computer rooms, petroleum and petrochemical systems, and rail transit
systems.
Topology of H3G-TH Battery Monitoring System
Features of H3G-TH Lead Acid Battery Monitoring System
Thermal runaway AI analysis and early warning
Advanced low power consumption design
AI data analysis
High-accuracy SOC/SOH
Function of H3G-TH Battery Monitoring System
Thermal runaway
Charge/discharge current
String voltage
Float current
SOC/SOH
Cell voltage
Cell temperature
Ambient temperature
Intelligent equilibrium
Cell internal resistance
Specification of H3G-TH Battery Monitoring System
Measuring content Range Accuracy Resolution
Sting voltage 20~800V ±0.5% 0.1V
Cell voltage 1.2V,2V,6V,12V ±0.1% 0.001V
Cell internal resistance 50~65535μΩ ±2%(repetitive accuracy) 1μΩ
Temperature -5~+99.9°C ±1°C 0.1°C
Charge/Discharge current ±1500A ±1% 0.1A
SOC/SOH — ±5% 1%