Tests for Current Transformer:
1)Excitation curve and parameters test
2)Turns ratio test
3)Ratio and phase error test
4)Polarity mark check
5)Winding resistance measurement
6)Secondary loop burden measurement
7)Error line curve test for protection CT
8)Transient CT parameters test
9)CT nameplate guess
10) Saturation hysteresis loop curve measurement
Tests for Voltage Transformer:
1) Turns ratio and phase angle error test
2) Polarity test
3) Secondary burden test
4) Winding resistance test
Applications of CT/PT Analyzer:
1) CT nameplate check
2) CT parameters check in work burden
3) CT transient parameters analysis
4) CT ratio and phase error calibration
5) PT routine test
1) Test standards: IEC60044-1, IEC60044-6, IEC60044-2, IEC60044-5, C57.13
2) Power supply: AC220V±10%, 50/60Hz±10%
3) Voltage output: 0.1~180V (AC)
4) Current output: 0.001~5A(RMS)
5) Power output: 500VA
6) Maximum knee voltage measurement: 45KV
7) Current measurement:
Range: 0~10A (automatically change range in 0.1/0.4/2/10A)
Error: <±0.1%+0.01%FS
8) Voltage measurement:
Range: 0~200V (automatically change range in 1V/10V/70V/200V)
Error: < ±0.1%+0.01%FS
9) Turns ratio measurement:
Range:1~35000
1~2000 error<0.05%
2000~5000 error<0.1%
5000~35000 error<0.2%
10) Phase measurement: error: ±2min; resolution: 0.01min
11) Winding resistance measurement:
Range: 0~8kΩ (automatically change range in 2ohm/20ohm/80ohm/800ohm/8kohm)
Error: < 0.2%RDG+0.02%FS
Maximum resolution: 0.1mΩ
12) Temperature measurement:-50~100 Celsius degree; error<3 Celsius degree
13) CT Secondary burden:
Range: 0~160ohm (automatically change range in 2ohm/20ohm/80ohm/160ohm)
Error: <0.2%RDG+0.02%FS
Maximum resolution: 0.001ohm
14) PT Secondary burden:
Range: 0~80kohm (automatically change range in 800ohm/8kohm/80kohm)
Error :<0.2%RDG+0.02%FS
Maximum resolution: 0.1ohm
15) PT ratio measurement:
Range: 1~35000
1~5000 error<0.2%
5000~35000 error<0.5%
16) PT phase angle test: error < 9min
17) Memory capacity: >1000 groups test results
18)Working condition: temperature: -10℃~50℃; moist: ≤90%
19) Size: 485mm×356mm×183mm
20) Weight: <15kg
GDVA-405 Automaatic Current Transformer and Potentional Tranformer Tester, CT PT Analyzer Description GDVA-405 CE Certificate Automatic Current Transformer CT and Potentional Transformer PT Tester Application Tests for current transformer Excitation curve and parameters test ...
Product Features 1.CT/PT Analyzer,5.7inch LCD screen display. 2.Full functions, satisfy all kinds of CT(protection CT, measuring CT, TP) test requirements, such as excitation characteristic test, turn ratio, polarity, secondary winding resistance, secondary burden, ratio error, ...
KV Grid Tester Co.,Ltd is a high- technology company combines research , production and commerce as one. We are professional manufacture of electric equipments (design and production). KV Grid Tester Co.,Ltd supplys advanced HV test equipments and detection instruments for ...