Remark: outline dimension of boiler body excludes the length of burners.
mm
2766
2500
2060
2060
1850
1770
H
mm
2400
2216
1900
1902
1751
1384
W
mm
5010
4740
3870
3510
2966
2440
L
Outline dimension of boiler body
14
Kg
7190
5110
3160
2830
2230
1300
Water capacity of boiler
13
class
<1
Ringelmen blackness
12
/
3N-50Hz 400V
3N-50Hz 400/230V
Applicable power supply
11
Kg/h
278
208
138
105
70
35
60# heavy oil
Nm3/h
635
476
318
238
159
78
City coal gas
Nm3/h
122
91
61
45
30
15
Liquid gas
Nm3/h
312
234
156
117
78
39
Natural gas
Kg/h
263
197
131
99
66
33
Light diesel
Fuel consumption
10
/
Light oil, natural gas, liquid gas, city coal gas, heavy oil
Applicable fuel
9
/
2 stage fire
1 stage fire
Adjustment mode of combustion
8
/
Autoignition, pressure fired combustion fully automatic running
Mode of combustion
7
t/h
480
360
288
240
192
144
Circulating flow
6
%
>90
Thermal efficiency of boiler
5
20, 105
Rated feed water temperature
4
194
184, 194
184
170
Rated steam temperature
3
MPa
1.25
1.0, 1.25
1.0
0.7
Rated working pressure
2
MW
4
3
2
1.5
1.0
0.5
Rated evaporation
1
WNS4
WNS3
WNS2
WNS1.5
WNS1.0
WNS0.5
unit
data
Item
No.
steam boiler parameter
rated outlet/inlet temperature: 95-130/70 degree. rated outlet pressure: 0.7-1.6MPa; rated thermal output: 0.7-14MW;
rated evaporation: 1-20t/h, |
steam boiler parameters:
rated evaporation: 1-20t/h,
rated steam pressure: 0.7-1.6MPa;
rated steam temp.: saturated temp.
Style: | Horizontal |
Structure: | Fire Tube |
Output: | Steam |
Model Number: | WNS series |
Place of Origin: | China (Mainland) |