Technical parameters:1) Rated evaporation: 35MT/h2) Rated vapor pressure: 3.82MPa3) Rated vapor temperature: 450oC4) Vapor working pressure in the boiler: 4.21MPa5) Feeding water temperature: 150oC6) Feeding water pressure: 4.61MPa7) Hot air temperature: 141oC8) Continuous waste discharging rate: 2%9) The designed efficiency of the boiler set: 80%Applicable fuel specifications:1) Designed fuel: lean coal (soft coal is also available) 2) Cy: 58.21%3) Hy: 2.91%4) Oy: 2.51%5) Ny: 1.64%6) Sy: 0.68%7) Ay: 26.57% 8) Wy: 7.48%9) Vr: 16 - 18% 10) QyDW: 21,094kJ/kg (5,038kcal/kg)11) T1: >1,200oC12) T2:
Main criterion for coal chain-grate boiler is WB-35 / 3.82-M
Usage: | Power Station |
Place of Origin: | China |