The inner area of the boiler is maintained as a vacuum at all times. Unlike a high pressure boiler, it poses no danger of accident.
|
|
|
|
An adequate amount of heating water is injected to the boiler and maintained at a vacuum. As the burner heats up the heating water, pressurized vapor is
generated and the heat is transferred to the heat exchanger for hot baths and heating.
|
|
|
|
The heat exchanger repeats the cycle of heating water, pressurized vapor and heat exchange and indirectly transfers the heat to the pressurized vapor. .
|
|
|
|
The vacuum hot water boiler is frequently used for heating and hot baths. It is widely used for hotels, pools, dorms and public baths requiring clean hot
water.
|
|
|
|
|
|
Model
|
B&B-VW
|
10
|
20
|
30
|
40
|
50
|
60
|
80
|
100
|
120
|
Rated evaporation
|
103kcal/hr
|
100
|
200
|
300
|
400
|
500
|
600
|
800
|
1000
|
1200
|
Insulation area size
|
|
4.5
|
8
|
11.3
|
12.8
|
13.7
|
16.3
|
19.2
|
20.7
|
23.2
|
Fuel consumption
|
B/C
|
/hr
|
12.4
|
24.8
|
37.2
|
49.6
|
62
|
74.4
|
99.2
|
124
|
148.8
|
LNG
|
N/hr
|
10.4
|
20.8
|
31.2
|
41.6
|
52
|
62.4
|
83.2
|
104
|
124.8
|
Fuel Diameter
|
B/C
|
A
|
15
|
20
|
20
|
20
|
20
|
25
|
25
|
25
|
25
|
LNG
|
A
|
20
|
20
|
25
|
25
|
25
|
25
|
40
|
40
|
40
|
Outlet gas duct
|
mm
|
150x200
|
160x300
|
180x300
|
200x300
|
200x300
|
200x300
|
250x300
|
250x350
|
280x400
|
Chimney
|
mm
|
200
|
250
|
250
|
300
|
300
|
300
|
350
|
430
|
430
|
Max pressure
|
m
|
|
|
|
|
70
|
|
|
|
|
Control System
|
-
|
ON-OFF / HIGH-LOW
|
Safety
|
-
|
|
For heating
|
Max pressure
|
m
|
70
|
Thermal capacity
|
103kcal/hr
|
100
|
200
|
300
|
400
|
500
|
600
|
800
|
1000
|
1200
|
Fluid amount
|
/hr
|
10
|
20
|
30
|
40
|
50
|
60
|
80
|
100
|
120
|
Diameter of the heating inlet and outlet
|
A
|
32
|
32
|
40
|
50
|
50
|
65
|
80
|
80
|
80
|
For hot bath
|
Max pressure
|
m
|
70
|
Thermal capacity
|
103kcal/hr
|
100
|
200
|
300
|
400
|
500
|
600
|
800
|
1000
|
1200
|
Fluid amount
|
/hr
|
1.67
|
3.33
|
5.0
|
6.67
|
8.33
|
10.0
|
13.3
|
16.7
|
20
|
Diameter of the heating inlet and outlet
|
A
|
32
|
32
|
40
|
40
|
50
|
65
|
80
|
80
|
80
|
|
|
1. These specifications are subject to change depending on the customer's request and for the purpose of quality improvement.
2. Gas supply pressure is 2,000~4,000 mmA1
|
|
|
|