l Or add the injection valve to regulate the injection liquid to distribute parts of refrigerant entering into the suction tube to absorb heat from evaporator, thus reducing the temperature of the discharge gas.
l Bypass the hot gas to the inlet of the evaporator to increase temperature of the outlet of the evaporator, enhance supplying liquid volume and decrease temperature of the extract air.
Suggestion of assembly
In the process of loading and unloading described as above, in case that the compressor operates in the period when evaporator lowers the load, the evaporating pressure (less than 4bar) is increased to 4bar. The pressure drop decreasing between the discharge and suction reduce load of the compressor resulting in energy saving.
CGX functioned as regulate energy
The inlet of the CGX Discharge-bypass valve is connected to the discharge pressure, and the outlet to the outlet or inlet of evaporator (Equivalent to extract pressure). Under this condition, the CGX is closed when evaporator loading; Because of decreasing evaporate pressure with a period of operation of the compressor, that is, it requires less power of the compressor because the expansion valve throttle turns to smaller, the evaporating pressure also becomes lower. When lowering than the set value, CGX is opened automatically. Parts of discharge gas of the compressor are by-passed to the inlet or outlet of evaporator.
CGX used as throttling valve to regulate energy
If the inlet of the Model CGX Discharge-bypass valve is connected to the condensing pressure and outlet to the inlet of evaporator, that is, the normal layout of thermal expansion valve. Under the condition, the CGX valve is closed when system turning off due to higher evaporating pressure; and the CGX will open automatically after compressor turning on due to evaporate pressure decreasing step by step. The refrigerant flows into the evaporator through the throttling hole of CGX. After the evaporator absorbs heat, the increasing evaporating pressure makes the valve closed. Once again, operation of the compressor makes evaporating pressure decreased and the valve turns to open status. During the operation, the valve always keeps the dynamic balance, maintaining the evaporating pressure constant approximately at the setting point. The variation situation of the evaporating pressure has something to do with the volume of the valve, regardless of the influence of the condensing pressure (Or environment temperature) .
CGX used as expansion valve under the fixed pressure
The CGX Discharge-bypass valve can open or close automatically while outlet pressure varies to ensure the outlet pressure constant on the setting point regardless of the change of the inlet pressure (within a certain range).
Function
l Maximum working pressure: 28bar.
l Suitable for HFC and HCFC
l SAE and ODF connecting .
l The CGX Discharge-bypass valve is capable to maintain the minimum evaporating pressure.
l The CGX Discharge-bypass valve can be used as automatic expansion valve under fixed pressure to maintain the fixed evaporation pressure (temperature).
l The CGX Discharge-bypass valve is used in the refrigerating system, which is not equipped with unloading device for the system load adjustment.
General
Discharge-bypass valve
Discharge-bypass valve
used in the refrigerating system, which is not equipped with unloading device for the system