GMG ROOF TOP AIR CONDITIONER

GMG SPECIFICATIONS FOR ROOFTOP PACKAGE UNIT
Model Name PRC-8MYA PRC-10MYA PRC-12MYA PRC-15MYA PRC-20MYA PRC-24MYA PRC-32MYA
Power Supply 3 ph / 4 pole / 380-415V / 50HZ
Total cooling capacity kW 24 31 34 48 62 68 110
Btu/h 81900 106000 116000 163800 199700 232000 375000
kcal/h 20600 26600 29200 41280 53320 58480 94600
Sensible cooling capacity kW 19 25 27 38 50 54 88
Btu/h 64800 85300 92000 133100 170000 184000 300000
kcal/h 16300 21500 23200 33540 43000 46400 75600
Total heating capacity   (Gross) kW 25 32 35 Bitmap
50
63 70 114
Btu/h 85300 109000 119000 170000 215000 238900 389000
kcal/h 21500 27500 30100 43000 54180 602000 98000
Capacity steps % 100-0 100-50-0
Refrigerant R22
Refrig Control Expan. Valve Model / Size TCLE7.5HCA TCLE12HCA TCLE7.5HCA TCLE12HCA TRAE20HCA
External finish Acrylic resin coating
Colour Munsell 4511
Dimension Height mm 1330 1500 1500 1310 1660 1660 1950
Width mm 1300 1480 1480 1990 1980 1980 2220
Depth mm 1450 1590 1590 1670 2050 2050 2320
Net weight kg 350 480 500 700 1200 1300 1600
Compressor Type Scroll
Compressor Make  Daikin Daikin Daikin Daikin Daikin Daikin Performer
Compressor Model JT236D JT315D JT335D JT236D JT315D JT335D SY240-4
No. X Motor output kW 1 X 6.5 1 X 8.5 1 X 9.0 2 X 6.5 2 X 8.4 2 X 9 2 X 17
Evaporator  Cross fin coil
Evaporator Fan Model KDF2.5WS KDF2.8WS KDFQ2.5 KDFQ3.15 KDFQ3.15 KDFQ3.5
Evaporator Fan Motor Supply 3 ph / 4 pole / 380-415V / 50HZ
No. X Motor output kW 2 X 0.55 2 X 1.0 2 X 1.0 2 X 1.5 2 X 3.0 2 X 3.0 2 X 4.0
Evaporator fan air flow CMH 4500 6001 6001 9000 11880 12960 19800
CFM 2600 3529 3529 5294 7000 7600 11700
L/S 1250 1667 1667 2500 3300 3600 5500
External static pressure mmAq 10 10 10 25 20 20 25
Pa 100 100 100 250 200 200 250
Condenser Cross fin coil
Condenser Fan Type Propeller direct drive
Condenser Fan Model LZF630-30X6 LZF7.1-42X6 LZF7.1-42X6 LZF630-30X6 LZF7.1-42X6 LZF7.1-42X6 CFA800-6T
Condenser Fan Diameter mm 630 710 710 630 710 710 800
Condenser Fan Speed  rpm 930 930 930 930 930 930 945
Condenser Fan Motor Three phase cage induction motor
No. X motor output kW 1 X 0.55 1 X 1.1 1 X 1.1 2 X 0.55 2 X 1.1 2 X 1.1 2 X 1.72
Condenser fan air flow CMH 9972 14000.4 14000.4 19980 23760 23760 43920
CFM 5882 8235 8235 11760 14000 14000 25800
L/S 2770 3889 3889 5550 6600 6600 12200
Drain connection mm 21 21 21 34
Sound pressure level dB(A) 71 72 72 74
Evap Coil Sytem 1 / 2 Tube Size DIA 3/8"
Spacing FPI 12
Rows 4
Length mm 1100 1200 1200 1710 1770 1770 2000
Height mm 600 600 750 800 800 900 1200
Circuits 12 12 15 16+16 16+16 18+18 24+24
Cond Coil System 1 / 2  Tube Size DIA 3/8"
Spacing FPI 12
Rows 3 3 3 4 4 4 4
Length mm 1730 2010 2010 1169 1254 1254 1359
Height mm 1000 1125 1200 1125 1300 1400 1800
Circuits 20 15 16 15 26 28 36

GMG ROOF TOP AIR CONDITIONER

  • Capacity:27000 btu up
  • Brand Name:GMG
  • Model Number:PRC-8MYA
  • Cooling/Heating:Cooling/Heating
  • Type:ROOF TOP AC
  • Power Type:AC
  • Power Source:Electrical
  • Country:South Korea
  • telephone:82-2-22427484
Capacity: 27000 btu up
Brand Name: GMG
Model Number: PRC-8MYA
Cooling/Heating: Cooling/Heating
Type: ROOF TOP AC
Power Type: AC
Power Source: Electrical
*Your name:
*Your Email:
*To:GMGATEWAY, INC.
*Subject:
*Message:
Enter between 20 to 3,000 characters. English only.     Characters Remaining: 0 / 3000
*Enter the secure code shown below Mfrbee security Image      Reload Image

We do inquire for you , please wait ...

GMG FLOOR STANDING TYPE AIR CONDITIONER

Certification:SASO Capacity:27000 btu up Certification:SASO Cooling/Heating:Cooling/Heating Type:Floor Standing Air Conditioners GMG MODERN LOOK FLOOR STANDING TYPE AIR CONDITONER ...

Come From GMGATEWAY, INC.

GMG MIRROR FINISHED AIR CONDITIONER

Capacity:18000-24000 btu Certification:CE Certification:CE Cooling/Heating:Cooling/Heating Type:Split Wall Mounted Air Conditioners Power Source:Gas GMG MIRROR PANEL WALL SPLIT AIR CONDITIONER ...

Come From GMGATEWAY, INC.

Sell Gmg Luxury Air Conditioner

Optional functions: 1) Negative Ion: Create fresh air with Negative ion.2) Body feeling: Let the room temperature changes according to your body's temperature. 3) Auto-restart: Let the aircon reture to the set mode after a sudden out of power. 4) Anti-bacterial filter: Purify ...

Come From GMGATEWAY, INC.