3.If the product improvement brings to the change of the parameters ,please refer to the nameplate.
Remarks:
1.Rated cooling test conditions :environmental dry ball temperature 35oC,wet ball temperature 24oC, inlet water temperature 12oC,outlet water temperature
7oC.
2.Rated heating test conditions :environmental dry ball temperature 7oC,wet ball temperature 6oC, inlet water temperature 40oC,outlet water temperature
45oC.
-7~43
oC
Ambient condition
DN80
mm
Diameter,water pipe
1
layer
Stacking layers
2080*1030*2080
mm
Packing dimension
2025*1030*1995
mm
Unit dimension
920
kg
Net weight
66
dB(A)
Noise
Sroll compressor
Compressor type
10.3
m3/h
Circulating water flow volume
23.5
kW
Rated power input
65
kW
Heating capacity
Heating
23
kW
Rated power input
60
kW
Cooling capacity
Cooling
3N-380V 50Hz
Power supply
KLRS-60F2
Model
Technical Specifications:
1.Cooling&heating.
2.Heat return technology, improve heating operation in low temperature.
3.Expansion valve regulates flow of refrigerant precisely.
4.Freely set openning cycle time in advance.
5.Unit runs automatically according to set water temperature.
6.Prevent freezing automatically in winter.
7.Modular design,free combination.
Product Features:
1.Cooling&heating
2.Heat-return technology
3.High efficience with special compressor
4.Expansion valve
try water chiller to get through more products
Supply Ability: | 10,000 Unit/Units per Month |
Payment Terms: | L/C,T/T |
Heating type: | Circulating heating |
Model Number: | KLRS-60F2 |
Brand Name: | Honny |
Installation: | Freestanding |
Type: | Air Source Heat Pump |
Place of Origin: | Zhejiang, China |
Advantages 1. The UVLED area light source adopts LED chip imported from South Korea; LED lamp beads have the advantages of high energy, strong illumination and long service life; 2. Single-wavelength LED light source is used for irradiation The conventional wavelength is 365nm, ...
Come From Futansi (Shanghai) Electronic Technology Co., Ltd.
The air-cooled chiller adopts a finned condenser, which has fast heat conduction and good heat dissipation effect without the need to provide cooling water. It can provide ice water at 5~35℃, and the low temperature type can be as low as 3℃ (the temperature difference does ...