New Refrigerant (R410A)
This air conditioner adopts a new HFC type refrigerant (R410A) which does not deplete the ozone layer.
1. Safety Caution Concerned to New Refrigerant
The pressure of R410A is high 1.6 times of that of the former refrigerant (R22). Accompanied with change of
refrigerant, the refrigerating oil has been also changed. Therefore, be sure that water, dust, the former refrigerant
or the former refrigerating oil is not mixed into the refrigerating cycle of the air conditioner with new refrigerant
during installation work or service work. If an incorrect work or incorrect service is performed, there is a
possibility to cause a serious accident. Use the tools and materials exclusive to R410A to purpose a safe work.
2. Cautions on Installation/Service
(1) Do not mix the other refrigerant or refrigerating oil.
For the tools exclusive to R410A, shapes of all the joints including the service port differ from those of the
former refrigerant in order to prevent mixture of them.
(2) As the use pressure of the new refrigerant is high, use material thickness of the pipe and tools which are
specified for R410A.
(3) In the installation time, use clean pipe materials and work with great attention so that water and others do
not mix in because pipes are affected by impurities such as water, oxide scales, oil, etc. Use the clean
pipes.
Be sure to brazing with flowing nitrogen gas. (Never use gas other than nitrogen gas.)
(4) For the earth protection, use a vacuum pump for air purge.
(5) R410A refrigerant is azeotropic mixture type refrigerant. Therefore use liquid type to charge the refrigerant.
(If using gas for charging, composition of the refrigerant changes and then characteristics of the air conditioner
change.)
3. Pipe Materials
For the refrigerant pipes, copper pipe and joints are mainly used. It is necessary to select the most appropriate
pipes to conform to the standard. Use clean material in which impurities adhere inside of pipe or joint to a
minimum.
(1) Copper pipe
The pipe thickness, flare finishing size, flare nut and others differ according to a refrigerant type.
When using a long copper pipe for R410A, it is recommended to select Copper or copper-base pipe without
seam and one with bonded oil amount 40mg/10m or less. Also do not use crushed, deformed, discolored
(especially inside) pipes. (Impurities cause clogging of expansion valves and capillary tubes.)
Use the flare nuts which are attached to the air conditioner unit.
(2) Joint
The flare joint and socket joint are used for joints of the copper pipe.
The joints are rarely used for installation of the air conditioner. However clear impurities when using
MMK AP00 72-92-122 H
BL121AC gateway supports connection and collection of multi-brand air conditioners, and uploads data to OPC UA for remote monitoring. The main functions of the cloud thermostat include cloud sensing (room temperature), cloud management (switching on and off air conditioners, ...
Come From Beilai Technology Co.,Ltd
LG AP-C308KLA0 30,000W Standing Air Conditioner 220-240 VOLTS NOT FOR USA 220-240Volt / 50 Hertz Power Supply R410A Refrigerant Quiet Cooling Cooling Capacity: 25000 Btu/h Dehumidification Capability For Indoor or Outdoor Use Product Information Product Type: Floor Standing ...
Come From World Wide Voltage
The Ethernet IO Modules suitable for IIOT Applications and Industrial Automation systems. In Traffic Tunnel Monitoring and control system, using the Ethernet IO Module can easy to form the whole ...
Come From BLIIOT