Description
The VOICE agent remote alarming module is a compact device designed for DIN rail mounting with a 230V AC power supply. The VOICE agent is equipped with 16 iputs for 24VDC. Up to eight inputs can be
switched to analog inputs. Against this are four digital relay outputs (e.g. collective- or hornoutput). All operating states and communication activities are shown in the display. Of course, the
VOICE agent is also a solution to expand an existing system.
All events are recorded in a log memory. This can be used to find out when an alarm arose and which subscriber acknowledged it.
Voice messages are transmitted via the analog telephone network. The subscriber line can be monitored so as to activate the system output should it be disconnected. A test message can be sent at
periodic intervals to test device operation.
To ensure proper function during power blackout, the VOICE agent has an integrated battery charge controller for an external connected battery pack. The battery conditon is monitored.
The actual status of the in- and outputs is visualised in the browser. Additionally, the value of analogue inputs is shown.
A web browser is used for programming the system. This means that no software needs to be installed or updated. The VOICE angent can be programmed and maintained over the network or the telephone
line.
Programming
Since all the programming takes place fully in the browser, there is noneed to purchase software and updates. The configuration comes withgraphics and is menu-based. 3 pikett groups are
available for the alarmfunction, each having 10 subscribers. A separate language file can bespecified for each of the 16 inputs. The fault message procedure iscarried out in accordance to DIN
19235. Delay times for the inputs,triggering the alarm and also for the jump to the next subscribers inthe alarm chain. Each subscriber in the alarm list can acknowledge thefault by entering a code
(DTMF tones), thus stopping further processingof the list.
Using the front mounted knob enables the setting of parameters likephone numbers of alarm recipients. This access is protected by an 4 to6 digit code
Technical Data
Iputs
|
Total 16, up to 8 analogue
|
Digital inputs
|
24VDC NO or NC
|
Analogue inputs
|
0-10V or 0-20mA with shunt
|
Outputs
|
4 potential free relays
|
Switching capacity, outputs
|
Max. 6A / 230VAC AC1
|
Supply voltage
|
230VAC (100-240VAC / 47-63Hz)
|
Power consumption
|
Max. 10W
|
Internal signal voltage
|
15VDC internally generated
|
External signal voltage
|
24VDC max.
|
Phone line
|
Analogue a/b
|
Network LAN
|
Static IP-Address or DHCP
|
Battery charger
|
Integrated for 12V accumulator up to 3Ah
|
Display
|
3 Row-LCD-Display backlit
|
Number of speech files
|
32
|
Number of phone numbers
|
30
|
Number of alarm profiles
|
8
|
Time channels
|
8
|
Speech files formats
|
Usual uncompressed sound files like wav
|
Housing
|
Metal powder coated
|
Dimensions WxHxD (without connectors/knob)
|
175 x 90 x 59 mm
|
Dimensions WxHxD (with connectors/knob)
|
175 x 120 x 68 mm
|
Weight
|
Appr. 650g
|
Mounting position
|
Any
|
Mounitng
|
35mm DIN-Rail
|
Connectors
|
Screw-plugterminals max. 1,5mm2
|
Ambient temperature
|
0
|