A unique line of detectors providing true distributed and analyzing calibration and pre-alarm/alarm values, the SmartOne intelligent detectors communicate 100% digitally with the FenwalNET 2000.
Available in Photoelectric (spot type or duct), Ionization (spot type or duct) and Thermal models the detector pre-alarm/alarm set point (% per foot obstruction or thermal degree) levels are
factory-set in each unit and may be modified in the field. SmartOne Intelligent Detectorr Detector set points may also be controlled by the systems real-time clock, enabling sensitivities to vary
based on time-of-day, day-of-week and/or holiday schedules. Each detector is self-monitoring with drift compensation combating environmental conditions, contamination and/or electronic component
aging. if a detector drifts outside its compensation algorithm a distinctive "Drift Error" message and trouble signal will be generated. In addition to its unique communications, each detector
offers rapid alarm response (maximum 2.5 seconds) and Fail-Soft operation. Fail-Soft operation combats unlikely communication link failure between the FenwalNET 2000 and the individual detector; if
a failure were to occur, the detector would operate as a standard alarm point on a conventional type zone circuit. --------------------------------------------------------------------------------
SmartOne Addressable DevicesFenwal offers two addressable contact input device types and one addressable relay output device type. Operating with integral microprocessors providing true distributed
intelligence, each addressable device provides Fail-Soft operation to combat unlikely communication link failure between the FenwalNET