2 Class B (Style B) Initiating Circuits which may be configured as 1 Class A (Style D) circuits
2 Class A/B (Style Z/Y) Indicating Circuits with individual trouble indicators (1.25 Amps max. per circuit)
Each Indicating Circuit can be configured as Silenceable or Non-Silenceable. Audible may be configured as Steady, Temporal Code, California Code or March Time
Selectable alarm verification on initiating circuits
Output for 4-wire resettable regulated smoke power supply of 24 VDC 100 mA maximum
Output for RTI or Remote Annunciators of 24 VDC, 300 mA max, unfiltered
Built-in Walk Test operation
Auxiliary relay contacts for Common Alarm, Common Trouble and Common Supervisory. If no Supervisory circuits are enabled, the Supervisory relay becomes a second Alarm relay.