Type Immediate alarm type, Combustible catalytic sensor type, Explosion-proof type Power AC 220V/60Hz Gas type LPG, LNG, Town gas(Heavy),Town gas(light) Power consumption 8W Detecting range LEL
0~100 Density to alarm LEL 20 Alarm sign LED yellow light and buzzer sound Breakdown LED red light Reset method Automatic Output Voltage signal : 12VCurrent signal : 4~20mA Contact signal : COM,
NO, NC(250V,3A) Use place Boiler room, factory, Gas store room, other gas facilities Operating Temp. & Hum. -30~50, Rh95% tX Weight(kg) Dimensions(mm) W40 X H133 X D110 It consists with
explosion-proof detector that detects the gas leakage, and receiver that displays the gas density by receiving signal from detector. With digital density display method, it allows easy gas density
verification. Explosion-proof detector is used in a place with the danger of explosion. When alarming, it can operate with exterior equipment like fan or blinker light. By using the 4~20mA output
from gas leakage sensor, it can operate with computer. For the stable operation of sensor, it stabilized the sensor by using initial delaying circuit. It operates stably for the change of
temperature and voltage. With switching constant voltage method, it minimized the power consumption and stabilized the sensor. By delivering leakage signal to gas controller, it allows to stop up
the gas valve automatically.