SmokeBoss is a registered Rel-Tek trademark. Covered by Rel-Tek's US Patent 5,420,440.
Product name | Cat No. | Code |
SmokeBoss*100, complete | SB100 | 7.2530 |
add for digital meter installed | -D |
|
Above with stand-alone AC power, trip relay board | RM420 |
|
strobe/horn alarm control. | -CTRL | 7.2531 |
Requires 10-30VDC power, 3-wire hookup, drawing about 35mA FS. MSHA evaluated I.S. under file nomenclature of "MultiBoss", Class G (Issue 95), H (Issue 32) and L (Issue 40) for hazardous methane areas. US patent No. 5,420,440 issued to Rel-Tek Corp. May 30, 1995. Call for more details or to order.
Analog smoke "monitoring" is better than an on/off "detecting". A slowly increasing signal can be responded to, well before an actual alarm. Data can be recorded and analyzed to define the trend parameters. Design minimize false alarms and desensitization from heavy dust. The IR source compensates for film/haze buildup on optical surfaces. If dust contamination ever occurs, brushing refreshes the optics. A handy optical calibrator provides a span reference. Housing measures 10x8x4.2" (254x203x107mm ); weighs 11 lbs (4.8Kg); has flanges for wall mount. A hinged lid make access easy.
fast field calibration without the need for costly gases.
detects smoky electrical and conveyor belt fires that may not generate enough CO to activate a CO sensor.
avoids false alarms from CO generated from diesel equipment, and
avoids false alarms from hydrogen gas from battery chargers,
Smoke monitoring offers important advantages over CO fire monitoring:
MSHA regs (CFR30, 75.340, 75.344, 75.351) for monitoring underground electrical equipment (i.e. power centers, battery chargers, pumps, etc.) permit smoke monitoring as alternate to CO monitoring, imposing a 5% per meter obscuration alarm level. One alarm level is specified.
The SmokeBoss*100 is a unique smoke monitor with analog 4-20mA output, linearly proportional to the visual obscuration caused by ambient smoke... the stated MSHA standard for fire (smoke) monitoring in underground mining. Developed over years of research, the SB100 offers a unique quantitative smoke monitoring capability. Most smoke detectors have only on/off alarms and are incapable of reporting gradually changing smoke levels. The SB100 monitors optical obscuration and generates an analog signal. The SB100 can be field cleaned and quickly calibrated using onboard optical filter.
Spec: smoke monitor, 10% optical density FS. Diffusion; 4-20mA output; dust resistant Field calibrate without gas or smoke.
Use SmokeBoss*100 units to back up CO and temperature monitoring for fire detection, especially important around conveyors which use modern polymer belt materials which generate a lot of smoke when jammed, but little CO or heat. Housed in a steel, wall mount box measuring 12x9x4.5". A digital meter is available for front panel numerical display in easy to read 1/2" high characters. Trip point relays may be added for stand-alone alarm and control operation. Quality, safety, performance and economy combine in this fine US-built product.
SmokeBoss, Ambient Smoke Monitor--Responds to optical obscuration of air due to smoke particles
Delivery Time: | Please Call or email |
Usage: | Smoke |
Brand Name: | Rel-Tek |
Place of Origin: | Pennsylvania United States |
SMOKE DETECTOR AUDIO (Cellular-Based) MONITORING DEVICE We Have Various Audio Mo ...
Come From DPL-Surveillance-Equipment.com