Public Announcement System "Rupor"

Public Announcement System "Rupor"
The Public Announcement System RUPOR is intended for broadcasting of announcements and notifications, recorded beforehand, to ensure security and order in case of fire or other extraordinary circumstances.
According to its capacities, the RUPOR system belongs to the class 3 (NPB 77-98 classification). If autonomous communication devices are used on the RUPOR basis, a composite system can be created, which would be classified in the class 4.
  • RUPOR can function in notification mode, initiated from the ORION controller or from an access control device (or relay module) of another fire alarm system. Operating in manual mode is also possible
  • RUPOR can function autonomously or within the ORION system
  • If RUPOR is used as a part of the ORION system, its control is accomplished through the interface RS-485
  • If RUPOR is used separately from the ORION system, its control is accomplished by interrupting one of the inbuilt alarm loops. Interruption of each loop corresponds to a particular annunciation scenario
  • RUPOR allows parameter programming: notification time and its delay, intervals between verbal messages, introduction to a verbal notification (sound signal to draw attention). Notifications themselves and their broadcasting priority can be programmed
  • Broadcasting of several notifications in a sequence according to their priority (an annunciation can be interrupted by another, more urgent one). Notifications with the same level of priority are broadcasted one after another. These possibilities can be used to modify the order of personnel evacuation (for example, if fire has involved one of the exits)
  • Acoustic modules are used as executive elements for verbal notifications
  • Detection of breaking into the housing (tampering); control of communicative channels and power supply
  • Status indication of the device, internal signaling loops, power supply etc.
  • Self-testing mode
  • Operating control tools can be locked
SPECIFICATIONS
  • Power supply voltage: 220 V/ 50 Hz
  • Built-in backup power source voltage: 12V
  • Min. working time from the built-in backup power source in standby mode: 24 hours
  • Min. working time from the built-in backup power source in annunciating mode: 3 hours
  • Min. total duration of one or several verbal notifications: 38 sec
  • Number of verbal notifications: 5
  • Reproducible audio frequency band 100-9000 Hz with max. variation 3 dB
  • Parallel notification channels number: 2
  • Nominal output power of an amplifier for one channel: 10 W
  • Nominal resistance of connected acoustic modules (loudspeakers): 4 Ohm
  • Min. resistance of wires connecting the device with acoustic modules: 3 Ohm
  • Alarm loops number: 4
  • Adjustable delay of notification start: 0-2 hours (with adjustment pace 1 sec)
  • Notification time adjustment: from 1 sec to 2 hours or without time limits
  • Max. dimensions 310x254x95 mm
  • Max. weight (with rechargeable battery): 8 kg

Min. working time from the built-in backup power source in annunciating mode: 3 hours

  • Country:Russian Federation
  • telephone:7-495-777-4020
Min. working time from the built-in backup power source in annunciating mode: 3 hours