NOTE: two 4AH batteries can be housed in the cabinet. Larger batteries require a separate battery box.
* AC POWER: 220 VAC, 50 Hz, 2.0 amps.
* Wire size: minimum 14 AWG (2.0 mm?) with 600-volt insulation.
* BATTERY: Sealed lead-acid batteries only.
* Maximum charging circuit: 27.6VDC @ 0.8 amp for normal flat charge.
* Maximum battery charger capacity: 18AH battery.
SPECIFICATIONS:
* Four to Sixteen Style B (Class B) Initiating Device Circuits (IDCs).
* All zones accept two-wire smoke detectors and any normally-open contact devices.
* Zones 1 - 16 configured as general alarm zones.
* All circuits are power-limited and supervised, meeting the latest ULC requirements using fuseless technology.
* Two built-in, Style Y (Class B) Notification Appliance (Signal) Circuits (NACs).
* NACs may be programmed: Silenceable. Non-Silenceable.
* Auto-Silence (program 5 to 20 minutes).
* 1.25 amps of NAC power.
* 3.0 amps of total system power.
* Alarm, Trouble and Supervisory, Form-C relay standard.
* 24-volt operation.
* Resettable four-wire smoke detector power @ 500 mA.
* Non-resettable power @ 500 mA.
* Integral battery charger capable of charging up to 18 AH batteries (batteries over 4 AH require use of the external battery backbox, or ULC listed equivalent).
* One-man walk-test programmable for silent or audible test.
* Disable/Enable control per IDC.
* Reverse polarity protection.
* Control buttons:
Mode/Test/ACK (Acknowledge) Alarm Silence/Reset
* LED indicators:
AC Power(green & yellow LED)
Fire Alarm(red LED)
Trouble(yellow LED)
Supervisory(yellow LED)
Signal Silence(yellow LED)
Battery Power(green & yellow LED)
Zone Disable(yellow LED)
NAC Fault(yellow LED)
NAC Disable(yellow LED)
Zone Alarm(one for each zone) (red LED)
Zone Trouble(one for each zone) (yellow LED)
FEATURES:
Fire Alarm Control Panel RC1000
1: Fire alarm control panel 2: Zones 1-16 Configured
3: All zone can eccept two-wire smoke detector and any N/O contact device
Delivery Time: | 15 days |
Package: | color box |
Supply Ability: | 1000 Piece/Pieces per Month |
Minimum Order Quantity: | 1 Piece/Pieces |
Payment Terms: | L/C,T/T,Western Union,MoneyGram |
Port: | shenzhen |
Model Number: | RC1000 |
Brand Name: | RICTRON |
Place of Origin: | Guangdong, China (Mainland) |
Model Number: | RC1000 |
Brand Name: | Rictron |
Place of Origin: | Guangdong China (Mainland) |
Manual Call Point, Designed for Fire Alarm Systems and Security Alarm system. Key Specifications/Special Features Available for flush or surface mounting Plastic film on glass Test key inserted from side Open circuit with series resistor Suitable for the majority of ...
Come From Shenzhen Puzhesi Technology Co., Ltd.
2 zone panel have Master panel and Slave panel. One Master panel can connect 31 Slave panel, and the Master panel could show the fire and fault of all slave panel. The slave panel can only show itself fire and fault.Key Specifications/Special Features Four Style B (Class B) ...
Come From Shenzhen Puzhesi Technology Co., Ltd.
Conventional Fire Alarm Control Panel with four Zones Key Specifications/Special Features Four Style B (Class B) Initiating Device Circuits (IDCs). All zones accept two-wire smoke detectors and any normally-open contact devices. One built-in, Style Y (Class B) Notification ...
Come From Shenzhen Puzhesi Technology Co., Ltd.