The S2000-PT unit is intended for status display of 10 fire extinguishing subsystem partitions within the integrated security system ORION.
MAIN FUNCTIONS AND COMPONENTS
-
50 double-color indicators and 8 one-color indicators (LED)
-
Double-color indicators display the following conditions for each of 10 sections under control: Fault; Attention; Fire; Start of the automatic fire-extinguishing
system; Hold up automatic fire-extinguishing system; Automatic system ON/OFF.
-
One-color indicators show the following conditions of the system: Fault, Attention, Fire, Failure, Hold up and Communication failure through the RS-485
interface
-
A Touch Memory reader can be connected to control access to operating tools of the fire extinguishing system
-
Operating tools of the fire extinguishing system includes 20 buttons: Start the fire extinguishing system; Start Cancellation; Automatic devices ON/OFF and
others
-
Sound signal activation after receipt of an alarm message from one or several partitions under control; possibility to forward the message to
operators
-
RS-485 double-wire interface enables:
-
forwarding messages on activation of the indication unit, box break-in (tampering); transmission of commands controlling the fire-extinguishing system to the
S2000 control panel or a computer
-
assignment of a network addresses and registration of configuration parameters (numbers of partitions, status of which is indicated)
-
using the unit within integrated fire-extinguishing systems
SPECIFICATIONS
-
Number of double-color status indicators of partitions 50
-
Number of one-color system indicators - 8
-
Power supply voltage 10,2 V to 28 V
-
Current consumption (standby mode) - 200 mA
-
Number of devices than can be connected to the series interface - 127
|