AThe model KSFH inline flame arrester is designed, manufactured and tested according to API 2000.British Standard Specification Code BS 7244, EN 12874 and FM(Factory Mutual) approved.The unit are
passive devices with no moving parts.They prevent the propagation of flame from the exposed side of the unit to the protected side by the use of a 316L stainless steel crimped metal ribbon type
flame cell element.This construction produces a matrix of uniform opening that are carefully constructed to quench the flame by absorbing the heat.This provides an extinguishing barrier to the
ignited vapor mixture.The KSFH flame arresters have specifically designed heat transfer characteristics for slow moving flames and low medium pressure fronts (low to medium deflagration).Inline
flame arresters can be installed either vertically or horizontally within a designated distance from the potential ignition extras.The standard flame cell is suitable for NEC group D or IEA IIA
gases. Cells for other gas groups are available as additional extras.The flame arresters are available with either aluminum, nodular iron, cast steel, 304SSss, 316SS and 316LSS housings, Iron and
steel housings are supplied epoxy coated. Meet USCG, IMO MSC/Circ,677 & EN 12874 requirementsDesigned for Explosion & Deflagration proofMaximum Capacity & Minimum Pressure dropCapability of
Bi-directional flow & flame arrestingQuick & Easy removable elementVery easy cleaning & maintenanceAvailable vertical & horizontal installationNo need forced push out pipe-lines for removing
elementHigh quality corrosion & chemical resistance