3.5.1 The architect may select and the Owner will pay an independent testing laboratory to examine firestopped areas to ensure proper installation prior to concealing or enclosing the firestopped areas.
3.5 INSPECTION
3.4.1 After completion of fire stopping work in any area, equipment shall be removed and walls, ceilings and all other surfaces not to receive fire stopping shall be cleaned of deposits of firestop materials.
3.4 CLEANING
3.3.1 Install fire stopping materials in accordance with the manufacturers' instructions.
3.3 INSTALLATION
3.2.1 Coordination: Coordinate the work with other trades. Fire stopping materials at penetrations of insulated pipes and ducts can be applied after insulation is in place. If insulation is
composed of combustible material, the thickness of fire stopping materials must be equivalent to that of the insulation. If the insulation is composed of non-combustible material, it may be
considered as part of the penetrating item.
3.2.2 Surface Preparation: Surfaces to be in contact with fire stopping materials shall be free of dirt, grease, oil, loose material or other substances that may affect proper fitting or the
required fire resistance.
3.2 PENETRATION:
PART 3 - EXECUTION
3.1 FIRESTOPPING LOCATIONS: Provide fire stopping in the following locations:
2.1.4 Substitutions: Submit in accordance with Section 01600.
Flame Stop V Putty/Caulk
Flame Stop, Inc.
924 Bluemound Rd.
Ft. Worth, TX 76131
2.1.3 Approved Product:
a. (F) ______ (T) ______ Time-rated floor or wall assemblies
b. (F) ______ (T) ______ Openings between floor slabs and curtain wall.
2.1.1 Flame Spread: 25 or less, ASTM E 84.
2.1.2 Fire Resistance and Hose Stream Tests: Fire stopping materials shall be rated "F" and "T" in accordance with ASTM E 814 or UL 1479. Rating periods shall conform to the following:
PART 2 - PRODUCTS
2.1 MATERIAL: Fire stopping material shall be asbestos free, 100% intumescent, have code approval under BOCA, ICBO, SSBC, NFPA 101, NFPA 70, and be capable of maintaining an effective
barrier against flame and gases in compliance with the following requirements:
1.3.1 Deliver materials to the project site in the original unopened containers or packages bearing the manufacturers' names, brand designations and product descriptions. Store materials under cover and protect from damage. Do not use damaged materials.
1.3 DELIVERY AND STORAGE:
1.2.1 Certificate of Compliance: Manufacturers' certificates of compliance that the materials meet the requirements specified.
1.2.2 Manufacturers' Data: Manufacturers' data for the fire stopping including fire stopping composition, performance characteristics, and installation procedures.
1.2.3 Shop drawings: Shop drawings showing material installation details including reinforcement, anchorage, and fastenings.
1.2 SUBMITTALS:
1.1.1 ASTM E 84 ..Surface Burning Characteristics of Building Materials
1.1.2 ASTM E 814 Fire Tests of Through-Penetrations Firestops
PART 1 - GENERAL
1.1 APPLICABLE PUBLICATIONS: The publication listed below form a part of this specification to the extent referenced. The publications are referred to in the text by the basic designation
only.
Specification Data
.1 APPLICABLE PUBLICATIONS: The publication listed below form a part of this specification to the extent referenced
.1 APPLICABLE PUBLICATIONS: The publication listed below form a part of this specification to the extent referenced |