1- On Delay: The output relay is initially de-energized and energized after an adjustable time delay, toff 2- Off Delay: The output relay is initially energized and de-energized after an adjustable
time delay, ton 3- Off Flasher: The output relay is initially de-energized and energized after an adjustable time delay, tonn, and stays energized for an adjustable period, toff, and then
de-energized. This loop is repeated until the device is powered off. 4- On delay with control input: The output relay is initially de-energized. A contact closure on K input triggers an adjustable
time delay, t, which energizes the output relay when expired. The output relay stays energized as long as the K input is active. Delay time, t, is cleared when the contact on K input opens. 5- Off
delay with control input: The output relay is initially de-energized and energized when a contact closure on K input is detected. A contact release on K input triggers an adjustable time delay, t,
which de-energizes the output relay when expired. Reclosure of the contact on K input before the time delay is expired restarts time delay, t, and keeps the output relay energized. 6- Rising edge
triggerred Off delay: The output relay is initially de-energized. A contact closure on K input both energizes the output relay and triggers an adjustable time delay, t, which de-energizes the
output relay when expired. During the time delay, K input is insensitive to state changes and becomes sensitive when time delay, t, expired. 7- Falling edge triggerred Off delay: The output relay
is initially de-energized. A state change of the contact on K input from closed to open both energizes the output relay and triggers an adjustable time delay, t, which de-energizes the output relay
when expired. During the time delay, K input is insensitive to state changes and becomes sensitive when time delay, t, expired. Time Relays-Multifunctional Technical ProductInformation Drawings &
Pictures Technical Product Information Technical Specifications Operating voltage 85..320 V AC Operating frequency 30..75 Hz Adjustment values 10s., 1m., 10m., 1h., 24h., 100h., s=sn / sec m=dk /
min h=saat / hour Time range ton,toff multiplier 0,05..1 Output contact 1 C/O 10A, 250Vac Operating temperature range -5..70