DYNATEK make Fire Engine Control panel is most compact user friendly, Highly reliable Fire Engine Control System. This is provided with Microcontroller based Diesel Engine Controller ECR16 with
Audio / Visual Alarm and Battery charger with Ammeter / Voltmeter.ECR 16 Controller is developed to start engine in Auto / Manual mode. In auto mode Controller continuously scans HYDRANT PRESSURE,
if it drops Controller cranks engine automatically through start relay. When engine reaches to set running condition it is automatically switched over to manual mode to stop the engine manually as
per the FIRE FIGHTING NORMS. It accepts input faults (Potential free Contact) like LLOP, over speed, over heat, etc. Any one of the input fault occurs, the corresponding LED window starts flashing
& gives signal to hooter relay for audio alarm. Hooter is provided in control panel for audio alarm. Input faults are site selectable (NO & NC). Dual rate flashing is provided for differentiating
the first & subsequent fault. The setting for ON TIME, OFF TIME & Attempt for CRANK can be done by DIP SWITCH provided on the backside of controller. Maximum four attempts can be selected.
DYNATEK make Fire Engine Control panel is most compact user friendly,