OK
No breakdown and flashover occurred on the combi.sample at 104kv,4h
No breakdown and flashover shall occur at 104kv
GB1103
A.C voltage withstand,4h
7
OK
No breakdown and flashover occurred on the combi.sample at 156kv,15min
No breakdown and flashover shall occur at 156KV
GB1103
D.C voltage withstand negative 15 min
6
OK
10 positive and 10 negative impulses at 250kv, No breakdown of the combi.sample occurred at 250KV
10 positive and 10 negative impulses at 250kv, flashover 1 time is allowed but not including total testing times
GB1103
Impulse voltage withstand 1.2/50us+10times
5
OK
39KV,
1. With 3-layer technology, more safe and reliable;
2. With long insulation tube, resolved the problem of creepage.