Only waterproof rated connectors will be considered for LV ABC insulated conductors. The dielectric behaviour shall be 6 kV under water. IPC shall be designed to tap-off LV ABC conductors complying
with HD 626 standard. A single tightening action to both the main and tap conductors shall connect them without removing the insulation. An insulated housing must encapsulate all live components
and must be anti UV stabilised black thermoplastic.
It must be suitable for application by one installer working alone with a 13 mm hexagon wrench. Stripping of insulation is avoided. Suitable for Aluminium and Copper Conductors Taping It must be
equipped with shear heads and flexible end caps. All components shall be unlovable. Tested for water tightness at a voltage of 4/6 KV for 30 minutes in water bath. Can be connect / disconnect on
live line, but on No load only.
The ABC system envisages use of insulated wired in place of bare conductors in the overhead distribution network. The system is
For fire-resistant or fire-retardant cables connecting branches (such as: Tunnel, construction and so on) Connection Quality: \"Hot spots\" are eliminated with a shear head screw that ensures the correct tightening torque. Easy installation: To install the whole series as only ...