OK
No breakdown and flashover occurred on the combi.sample at 25kv,15min
No breakdown and flashover shall occur at 25KV
JB/T8144.1
A.C voltage withstand, 15 min
11
As left
Heating for 5h,cooling for 3h.Conductors temperature is90-95 in water bath,9 cycles,Results refer to the following Test
Heating for 5h,cooling for 3h.Conductors temperature is90-95 in water bath,9 cycles
DL413
Sealing test
10
OK
No breakdown occurred on the combi.sample at 35kv,4h
No breakdown and shall occur at 35kv,4h
JB/T8144.1
A.C voltage withstand,4h
9
OK
No breakdown and flashover occurred on the combi.sample at 52kv,15min
No breakdown and flashover shall occur at 52KV
JB/T8138.1
D.C voltage withstand negative 15 min
8
OK
No breakdown of the combi.sample occurred at 105kv
10 positive and 10 negative impulses at 105kv,No breakdown
GB/T16927
JB/T8138.1
Impulse voltage withstand 1.2/50us+10times
7
OK
a,b,c <3pc
20pc max.at 13kv
JB/T8138.3
Partial discharge
6
OK
a,b,c <3pc
3pc max.at 9kv
JB/T8138.3
Partial discharge
5
As left
Conductors temperture is 95.Results refer to the following test
Heating for 5h,cooling for 3h.Conductors temperature is90-95,3cycles
JB/T8138.3
Load cycle
4
OK
a,b,c <3pc
20pc max.at 13kv
JB/T8138.3
Partial discharge
3
OK
a,b,c <3pc
3pc max.at 9kv
JB/T8138.3
Partial discharge
2
OK
No breakdown and flashover occurred on the combi.sample at 45kv,1min
No breakdown and flashover shall occur at 45KV
JB8144
AC withstand for 1 min
1
Joint
Results
Requirements
Test
Property
Item No
Heat-shrinkable power cable accessories testing for 10KV XLPE cable