Standard and Property for Using
The products can be produced according to our factory specification which is equivalent to the standard IEC60502. The factory can also design and manufacture special XLPE cable according to the
other standards required by the customers. They not only have excellent electric, mechanical properties, but also have powerful resistance against chemical corrosion, heataging and environmental
stress. Their structures are simple. The permissible maximum operating temperature is 90C. It is convenient for using, and they can be laid with no restriction of different elevation.
The Rated Voltage, No of Core and Range of sectional Area
Rate
Voltage(kv)
Sectional
Area(mm2)
No. Of Core
1st class 0.6/1 1.8/3 3.6/6 6/10 8.7/15 12/20 18/30 21/35
2nd class 1/1 3/3 6/6 8.7/10 12/15 18/20 - 26/35
1 Core 1.5-800 25-800 25-1200 25-1200 35-1200 50-1200 50-1200 50-1200
2 Core 1.5-185 25-185
3 Core 1.5-400 25-400 25-400 25-400 35-400 50-400 50-400 50-400
4 Core 2.5-400 25-400
5 Core 2.5-400 25-400
The Type and Main Application
Type Name Main Application
Cu Core Al Core
YJV
YJY YJLV
YJLV XLPE insulated, PVC or PE Sheathed Power Cable For laying indoor, tunnel, channel and undergroud, Unable to bear external mechanical force, but bear the traction force during laid
YJV22
YJV22 YJLV22
YJV22 XLPE Insulated, Steel Tape Armoured, PVC or PE Sheathed Power Cable For laying indoor, tunnel, channel and undergroud Able to bear external mechanical force, but unable to bear large pulling
force
YJV32
YJV32 YJLV32
YJLV32 XLPE Insulated, Fine Steel Wire Armoured, PVC or PE Sheathed Power Cable For laying in shaft with large difference of level. Able to bear external machanical force and maderate pulling
force
YJV42
YJV42 YJLV42
YJLV42 XLPE Insulated, Thick Steel Wire Armoured, PVC or PE Sheathed Power Cable Able to bear positive pressure and pulling force
Note: "ZR-"Include ABC three kinds of flame retardent cables, which are spectively indicated in "ZRA-" or "ZRB-" "ZRC-". For example: "ZRB-YJV""ZRA-YJV22".
Main Technical Quota
1. DC resistance: Conductor resistance of finished cable at 20Cper kilometer is not more than the following values.
Nominal Section
Area(mm2) 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400 500 630 800
Copper Core 12.1 7.41 4.61 3.08 1.83 1.15 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470 0.0366 0.0283 0.0221
Aluminum Core 18.1 12.1 7.41 4.61 3.08 1.91 1.20 0.868 0.641 0.443 0.320 0.253 0.206 0.164 0.125 0.100 0.778 0.0605 0.0469 0.0367
2. Voltage Test and Partial Discharge Test
Rate
Voltage Uo(kv)
Item
0.6/1 1.8/3 3.6/6 6/6
6/10 8.7/10
8.7/15 12/20 18/20
18/30 21/35 26/35
Voltage Test Voltage 3.5 6.5 12.5 21 30.5 42 63 73.5 91
Test Time 5 5 5 5 5 5 5 5 5
Partial Discharge Test Test Voltage - - 6.2 10.4 15.1 20.8 31.1 36.3 45
Discharge Capacity - - 10 10 10 10 10 10 10
One of the biggest wire&cable manufacturer in middle China,sales in Middle East,Africa,New Zealand,Austrarlia,Chile,Brazil......
Supply Ability: | 50 Kilometer per Month |
Minimum Order Quantity: | 1 Kilometer |
Payment Terms: | L/C,D/A,T/T,Western Union |
Jacket: | PVC |
Conductor Material: | Aluminum |
Type: | Low Voltage |
Insulation Material: | XLPE |
Brand Name: | TAIYANG |
Place of Origin: | Henan China (Mainland) |
Voltages up to 35kv PVC/XLPE Power Cable Brief Introduction PVC/XLPE power cable is used to transmit and distribute power in power transmission and distribution system of 35kV or lower. It is generally applied to the fields including power, construction, mines, metallurgy, ...