Construction
|
|
|
Conductor
|
:
|
Flexible copper wires, plain
|
Insulation
|
:
|
PVC
|
Core Identification
|
:
|
Different Colours
|
|
|
|
Electrical Parameters
|
|
|
Standard
|
:
|
TS 9758 HD 21,3 S3
|
Rated Voltage
|
:
|
300/500 V (H05V-K), 450/750 V (H07V-K)
|
Test Voltage
|
:
|
2kV-2,5kV
|
Temperature Range
|
:
|
-200C~+700C
|
Max. Short Circuit Temperature
|
:
|
1600 C
|
Min. Bending Radius
|
:
|
10xD
|
Part Number
|
Nominal Cross Section
|
No of Cores x Cross Section
|
Approx. outer Diameter
|
Approx. Cable Wieight
|
Conductor Resistance at 200C (Max)
|
Current Carrying Capacity in ground at 200C
|
Current Carrying Capacity on air at 300C
|
H05V-K
|
0,50
|
15x0,20
|
2,1
|
9
|
39,0
|
-
|
11
|
H05V-K
|
0,75
|
22x0,20
|
2,3
|
11
|
26,0
|
-
|
16
|
H05V-K
|
1,00
|
30x0,20
|
2,5
|
14
|
19,5
|
11
|
26
|
H07V-K
|
1,5
|
27x0,50
|
2,9
|
20
|
13,3
|
15
|
24
|
H07V-K
|
2,5
|
47x0,25
|
3,6
|
32
|
7,98
|
20
|
32
|
H07V-K
|
4
|
51x0,30
|
4,2
|
50
|
4,95
|
25
|
42
|
H07V-K
|
6
|
76x0,30
|
4,8
|
70
|
3,30
|
33
|
54
|
H07V-K
|
10
|
73x0,40
|
6,5
|
115
|
1,91
|
45
|
73
|
H07V-K
|
16
|
119x0,40
|
8,0
|
175
|
1,21
|
61
|
98
|
H07V-K
|
25
|
187x0,40
|
10,0
|
270
|
0,780
|
83
|
129
|
H07V-K
|
35
|
255x0,40
|
11,0
|
370
|
0,554
|
103
|
158
|
H07V-K
|
50
|
374x0,40
|
13,5
|
525
|
0,386
|
132
|
198
|
H07V-K
|
70
|
336x0,50
|
15,0
|
700
|
0,272
|
165
|
245
|
H07V-K
|
95
|
456x0,50
|
17,5
|
970
|
0,206
|
197
|
292
|
H07V-K
|
120
|
576x0,50
|
19,5
|
1200
|
0,161
|
235
|
344
|
H07V-K
|
150
|
696x0,50
|
22,0
|
1500
|
0,129
|
-
|
391
|
H07V-K
|
185
|
888x0,50
|
24,0
|
1860
|
0,106
|
-
|
448
|
It is used in connection of unsteady installation and equipment, in buildings, dry places, within tube, above and under plaster.