Construction |
|
|
Conductor | : | One or stranded copper conductor |
Insulation | : | PVC |
Rated Voltage | : | 300/500V (H05V-U), 450/750V (H07V-U/R) |
AC Test Voltage | : | 2-2,5 kV |
|
|
|
Electrical Parameters |
|
|
Standard | : | TS 97583 VDE 0281, IEC 60227, BS 6004, HD21,3 S3 |
Max. Operating Temperature | : | 700C |
Max. Short Circuit Temperature | : | 1600 C (max.5 sn.) |
Part Number | Nominal Cross Section | Approx. outer Diameter | Approx. Cable Wieight | Conductor Resistance at 200C (Max) | Current Carrying Capacity in ground at 200C | Current Carrying Capacity on air at 300C |
H05V-U | 0,5 re | 2,1 | 8 | 36,0 | - | 9 |
H05V-U | 0,75 re | 2,3 | 11 | 24,5 | - | 15 |
H05V-U | 1,0 re | 2,5 | 14 | 18,1 | 11 | 19 |
H07V-U | 1,5 re | 2,8 | 20 | 12,1 | 15 | 24 |
H07V-U | 2,5 re | 3,3 | 31 | 7,41 | 20 | 32 |
H07V-U | 4 re | 3,8 | 46 | 4,61 | 25 | 42 |
H07V-U | 6 re | 4,3 | 54 | 3,08 | 33 | 54 |
H07V-U | 10 re | 5,6 | 108 | 1,83 | 45 | 73 |
H07V-R | 10 rm | 6,0 | 111 | 1,83 | 45 | 73 |
H07V-R | 16 rm | 7,0 | 170 | 1,15 | 61 | 98 |
H07V-R | 25 rm | 8,5 | 260 | 0,727 | 83 | 129 |
H07V-R | 35 rm | 9,5 | 355 | 0,524 | 103 | 158 |
H07V-R | 50 rm | 11,0 | 505 | 0,387 | 132 | 198 |
H07V-R | 70 rm | 13,0 | 694 | 0,268 | 165 | 245 |
H07V-R | 95 rm | 15,0 | 938 | 0,193 | 197 | 292 |
In dry locations in conduit or under plaster. Not approved direct installation in plaster in switching and distribution station.
Jacket: | PVC |
Conductor Material: | Copper |
Application: | Construction |
Type: | Low Voltage |
Insulation Material: | PVC |
Model Number: | H05V-U / H07V-U |
Brand Name: | HUNKA |
Place of Origin: | Turkey |
H07v r cable, h07v-k cable, and h07v u cable are PVC electrical wiring, made of bare copper conductor and PVC insulation material, that conforms to European harmonized standards. The h07v cable is used for building, internal wiring of electrical switchboards, power distribution ...
Come From HENAN HONREY CABLE CO.,LTD
H05v-r cable, h05v k wire, h05v u cable is PVC electrical wiring, made of bare copper conductor and PVC insulation material, conforms to the European harmonized standard, used for building, internal wiring of electrical switchboards, power distribution cabinet and ...
Come From HENAN HONREY CABLE CO.,LTD
It is well known that the electric vehicle charging cable is an indispensable equipment for the charging of new energy electric vehicles and the carrier of power transmission. So, how is a qualified cable born? First of all, it is necessary to precisely twist multiple strands ...