for use up to to 2400 volts. All Type MV-90
cables are UL listed as intended for use in accordance with NEC Article 310-6 and
Table 310.63 in dry locations up to 90?C. They may also be used as rugged cables
in ducted 600 volt or 2400 volt series lighting circuits.
The 4, 6, and 8 AWG conductor cables are FAA approved for direct buried airport
lighting circuits in accordance with the FAA advisory circular 150/5345-7E.
FEATURES
1. CONDUCTORS
Soft drawn bare copper stranded to ASTM B 3 & B 8.
2. STRAND SHIELD
4 mil thick semiconducting tape longitudinally applied with 10%
or more overlap in accordance with the requirements of UL 1072.
3. INSULATION
Crosslinked polyethylene (XLPE) compound which is in accordance
with the requirements of UL 1072 and the National Electrical Code.
4. SURFACE MARKING
The jacket surface shall be printed or indented with:
DRAKA CABLETEQ USA-PA TAMAQUA CABLE TYPE MV-90
DRY SIZE (AWG) 2400 VOLTS NON-SHIELDED XLP (UL).
RATINGS
UL 1072 MV-90 DRY
ICEA S-96-659
DRAKA CABLETEQ USA-PA TAMAQUA CABLE TYPE MV-90
1
2
3
4
TYPE MV-90 POWER CABLE XLPE insulated conductor 8 to 4/0 AWG / 2400 volt |