The bending radius of single core cable should not be less than 20 times of the cable diameter; the bending radius of multi-core cable should not be less than 15 times of the cable diameter.
The ambient temperature under installations should not be below 0 oC.
Max.short-circuit temperature of the conductor shall not exceed(Max.5 seconds duration): 250 oC.
Max.permissible continuous operating temperature of conductor:90 oC
Rated power-frequency voltage U0/U:3.6/6kV-26/35kV
6). Operating characteristics:
5). Production range: Single core cable from 1.5mm2 to 800mm2; Multi-core cable from 1.5mm2 to 400mm2.
4). Nominal cross-sectional areas: 1.5mm2, 2.5mm2, 4mm2, 6mm2, 10mm2, 16mm2, 25mm2, 35mm2, 50mm2, 70mm2, 95mm2, 120mm2, 150mm2, 185mm2, 240mm2, 300mm2, 400mm2, 500mm2, 630mm2, 800mm2
Note: The armoured single core cables is only used for D.C. system. As for A.C. system, non-magnetic armour material should be applied.
Aluminium conductor, XLPE insulated, steel wire armoured, PE sheathed power cable
Copper conductor, XLPE insulated, steel wire armoured, PE sheathed power cable
YJLV33
YJV33
For laying indoors, in tunnel, in cable trench or direct in ground, able to bear external mechanical forces, but unable to bear large pulling force.
Aluminium conductor, XLPE insulated, steel wire armoured, PVC sheathed power cable
Copper conductor, XLPE insulated, steel wire armoured, PVC sheathed power cable
YJLV32
YJV32
Aluminium conductor, XLPE insulated, steel tape armoured, PE sheathed power cable
Copper conductor, XLPE insulated, steel tape armoured, PE sheathed power cable
YJLV23
YJV23
For laying indoors, in tunnel, in cable trench or direct in ground, able to bear external mechanical forces, but unable to bear large pulling force.
Aluminium conductor, XLPE insulated, steel tape armoured, PVC sheathed power cable
Copper conductor, XLPE insulated, steel tape armoured, PVC sheathed power cable
YJLV22
YJV22
Aluminium conductor, XLPE insulated, PE sheathed power cable
Copper conductor, XLPE insulated, PE sheathed power cable
YJLY
YJY
For laying indoors, in tunnel or cable trench, unable to bear external mechanical forces. Single core cable is not permissible to lay in magnetic duct.
Aluminium conductor, XLPE insulated, PVC sheathed power cable
Copper conductor, XLPE insulated, PVC sheathed power cable
YJLV
YJV
Applications
Designation
Type
3). Specification:
2). Voltage: 3.6/6kV; 6/10kV; 8.7/15kV; 12/20kV; 18/30kV; 21/35kV; 26/35kV
1). Standard: IEC60502, GB/T 12706
6kV-35kV XLPE insulated power cable
6kV-35kV XLPE insulated power cable is used for electric power transmission and distribution lines.
Delivery Time: | Depending on the quantity |
Package: | wooden drum; iron-wooden drum; iron drum |
Supply Ability: | 200 Kilometer per Month |
Minimum Order Quantity: | 2 Kilometer |
Payment Terms: | L/C,T/T |
Port: | NINGBO |
Jacket: | PVC |
Conductor Material: | copper or aluminium |
Application: | Underground |
Type: | medium/high voltage |
Insulation Material: | XLPE |
Model Number: | from 1.5sqmm to 800sqmm |
Brand Name: | KUKUN, QRUNNNING |
Place of Origin: | Zhejiang China (Mainland) |
XLPE electrical wire 4 core power cables are normally used in power transmission and distribution systems. The power cable 4 core XLPE cable is referred to as IEC60502 CU/XLPE/PVC 0.6/1KV. The circular conductor is applied for the size below 16mm² and the shaped conductor is ...
The structure of 10mm 4 core and earth cable+1 earth is designed for application where the earth wires are required according to customer requirements. These 4 core and earth cable are often referred 16mm xlpe 4 core +1 cables XLPE insulated with voltage 0.6/1000v or IEC60502 4 ...
XLPE insulated 3 core power cable is normally used in power transmission and distribution systems. The three core cable wires are referred to IEC60502 CU/XLPE/PVC 0.6/1KV. The circular conductor is applied for the size below 16mm² and the shaped conductor is applied for the ...