The Conoflow GT_2 Series Transducer accepts a DC voltage input and provides a
proportional 3-15, 3-17 or 6-30 PSIG (21-103, 21-186 or 41-207 kPa) output. The
input range is adjustable from a minimum of 0-5 VDC to a maximum of 0-60 VDC.
Note that there are two circuit boards provided for this unit. One for input signals
of 0-5 to 0-32 VDC and one for 0-33 to 0-60 VDC inputs. Two individual boards
are provided as a 1.5K resistor is added to the circuit board for the 0-33 to 0-60
VDC input to reduce power dissipation in the range potentiometer at these higher
inputs.
These transducers are available in either high or low flow capacity configurations
(Maximum Air Delivery Rate). The high capacity models incorporate a booster
DIMENSIONAL DATA - ADVERTISING DRAWINGS:
GT Series - High Capacity: A28-7
GT Series - Low Capacity: A28-9
GT Series - 2 Pipe Mounting Bracket: A28-22
relay which eliminates the need for additional boosters or relays when operating
air actuated valves or final control elements. The low capacity versions use a fixed
orifice and are utilized for input signals to pneumatic positioners. NEMA 3R
housing requirements are optional.
Design characteristics of quality and reliability are backed by Conoflows high
standard of manufacturing and years