It is a balance blend of sequestering agent which is mildly acid. It is a liquid product which must be administered gradually to the feed water tank by means of a chemical proportioning pump. It contains no heavy metals. ApplicationInjected directly into the boiler by means of a proportioning pump. This product, in addition to its being environmentally safe, is easily handled since it is non-hazardous and non corrosive. DosageNo initial dosage need to be applied to the boiler or feed water tank. The maintenance dosage is adjusted by means of a chemical pump to provide orthophosphate levels between 20 to 30 ppm (mg/l) in the boiler water. Maintain 2-3 ppm in the make-up water by using approximately 1 quart per 1,000 gallons.
LC 107 prevents scale formation in feed water lines to the boiler where hard water is used as make-up water. |