GDVA-405 Full Automatic CT PT Testing Equipment

Place Of Origin
China
Packaging
Standard wooden case and carton according to customer's requirement
Delivery
15 Working Days

Specifications:

Test standards: IEC60044-1, IEC60044-6, GB1208, GB16847, C57.13

♦ Power supply: AC220V±10%,50Hz/60Hz±10%

♦ Power output: 0.1~180V (AC)

♦ Current output: 0.001~5A(RMS)

♦Power output:300VA

♦Maximum knee voltage measurement; 45kv

♦Current measurement:

  1. Range:0~10A (automatically change range in 0.1/0.4/2/10A)
  2. Error <±0.1%+0.01%FS

Voltage measurement:

  1. Range:0~200 V (automatically change range in 1V/10V/70V/200V)
  2. Error < ±0.1%+0.01%FS

Turns ratio measurement:

  1. Range :1~35000,
  2. 1~2000 error<0.05%
  3. 2000~5000 error>0.1%
  4. 5000~35000 error<0.2%

♦ Phase measurement: error:±2min,resolution:0.01min

Coil resistance measurement:

  1. Range:0~8kΩ (automatically change range in 2ohm/20ohm/80ohm /800ohm /8kohm)
  2. Error< 0.2%RDG+0.02%FS
  3. Maximum resolution:0.1mΩ

Temperature measurement:-50~100 Celsius degree, error<3 Celsius degree

♦ CT Secondary burden:

  1. Range 0~160ohm (automatically change range in 2ohm/20ohm/80ohm/160ohm)
  2. Error <0.2%RDG+0.02%FS
  3. Maximum resolution 0.001ohm

PT Secondary burden:

  1. Range 0~80kohm (automatically change range in 800ohm/8kohm/80kohm)
  2. Error <0.2%RDG+0.02%FS
  3. Maximum resolution: 0.1ohm

PT ratio measurement:

  1. Range :1~35000,
  2. 1~5000 error<0.2%
  3. 5000~35000 error<0.5%

Saved data groups:>1000groups

Work condition: Temperature:-10℃~50℃, moist:≤90%

Size: 485mm×356mm×183mm

Weight: <15Kg

  • Country: China (Mainland)
  • Business Type: Manufacturer
  • Market:Asia
  • Founded Year:2009
  • Address:重庆南岸区南坪
  • Contact:Sunny Liu
*Your name:
*Your Email:
*To:重庆格纳迪设备有限公司
*Subject:
*Message:
Enter between 20 to 3,000 characters. English only.     Characters : 0 / 3000
*Enter the secure code shown below Mfrbee security Image      Reload Image

submiting now We do inquire for you , please wait ...